Power Conservation

Hospital has initiated several power conservation methods to conserve electricity.

Electrical Installation

Changes to Electrical Installation to Conserve Power

1) Street light
OLD system 150W × 120nos — 18KW/hour. In 10 hours average energy consumption 180KW.
Present system 150w was replaced with 30W: 30W × 120nos — 3.6KW/hour. In 10 hours average energy consumption 36KW.

2) Tube light
Old system 40W × 2000nos — 80KW. In 10 hours average energy consumption 800KW.
Present system 40W was replaced with 20W: 20W × 2000nos — 40KW. In 10 hours average energy consumption 400KW.

3) Dryers in Laundry
60KW heating elements was replaced by 30KW.

HVAC Installation

Changes to HVAC Installation to Conserve Power

Sr. No Description Action taken Energy savings Energy savings per day Energy saving per year 364 days at ₹8/unit
1 Cooling tower no1, Cooling tower no2, Cooling tower no3 Cooling tower has been replace – 2nos of 10 hp/7.5 kw motor to 1no motor of 12.5hp/10kw. 5 Kw/Hr An average working of cooling tower per day 12 hrs = 60 kw/day 21,840 kw/year — Rs 1,74,720
2 Radiology 2nos of AHUs 35TR with 12.5hp/10kw motor & 10hp/7.5 kw motor working contentiously in day time Inter connected the ducting of 2 AHUs and switched off one AHU permanently. 7.5 kw/Hr An average working of AHU per day is 12 hrs = 90 kw/day 32,760 kw/year — Rs 2,62,080
3 CTVS ICU and neuro ICU 100% Fresh air system converted into 70% Fresh air 30% Recirculated air system without effecting the standards. Disconnected 10hp/7.5 kw exhaust blower and Heat Recovery wheel of around 0.5 kw. 8 kw/hr ICU works 24 hrs per day — 192 kw/day 69,888/year — Rs 5,59,104
4 MS.OT – 4nos 100% Fresh air system converted into 70% Fresh air 30% Recirculated air system without effecting the standards. Disconnected 1hp/.75 kw exhaust blower and Heat Recovery wheel of around 0.25 kw. 1 kw/hr OT is working around 12 hrs per day — 12 kw/day 4,368 kw/year — 34,944
5 VFDs for Cath lab AHU-30TR-12.5HP/10KW, CCU AHU-30TR-10HP/7.5KW, Labor room AHU-30TR-10HP/7.5KW, CTVS ICU-15HP/12.5KW, Neuro ICU-15HP/12.5KW By introducing the VFDs in different location AHUs the efficiency improved in AHUs and an average and overall 0.5 kw has been saved. 3 kw/hr An average working AHUs all together 15 Hrs/day — 45 kw/day 16,380 kw/year — 1,31,040